Corrects line voltage conditions as low as 65V and as high as 150V to within 2% of selected nominal voltage
Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)
Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible)
external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included
PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of
additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control, remote reboot and UPS nominal voltage adjustment
Built-in Emergency Power Off (EPO) interface with cable
NEMA L5-30P input plug / NEMA 5-15R, 5-15/20R & L5-30R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks
Front panel LEDs offer current monitoring and battery charge level information
Network grade AC, TEL/DSL or ethernet line surge suppression
Field replaceable, hot swappable internal batteries and external battery packs
$250,000 Ultimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA capacity (kVA)
Output Watt Capacity (watts)
Output kW capacity
Output power factor
Crest Factor
Nominal Output Voltage(s)
Supported
Frequency compatibility
Frequency compatibility details
Output voltage regulation (line mode)
Output voltage regulation (Economy
line mode)
Output voltage regulation (Battery
mode)
Built-in UPS output receptacles
Built-in controllable switched load
banks
3000
3
2400
2.4
0.8
3:1
110V; 120V
50 / 60 Hz
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
+/- 2%
+/- 10%
+/- 2%
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)